Unleashing VPF Technology
Centralised air conditioners should ideally provide comfort and energy efficiency. Variable Primary Flow systems coupled with Pressure Independent Balancing and Control Valves deliver on both counts, says Ismail Serhan Ozten of Danfoss, who presents proof to support his assertion.
Centralised air conditioners should ideally provide comfort and energy efficiency. Variable Primary Flow systems coupled with Pressure Independent Balancing and Control Valves deliver on both counts, says Ismail Serhan Ozten of Danfoss, who presents proof to support his assertion.
Infrastructure challenge
It is to state the obvious that most commercial buildings have very low occupancy after office hours or during weekends. This renders operating centralised air conditioning systems during these times wasteful. The challenge is to run them efficiently.
In example 1 the building has 10 floors and all of them are occupied from morning till late afternoon. During evening time, a single floor is open for business. Thus, the centralised air conditioning system that distributes air for the entire building has to work for the sake of cooling only a single floor.
Modern building outlook requirements do not allow an additional air conditioning equipment to be displayed outside the building. Therefore, running a separate smaller air conditioning system is not an option. In such a scenario, the Variable Primary Flow system could be the answer.
Variable Primary Flow system: Introduction
Variable Primary Flow (VPF) system was commonly published in the 1990s and is superior to Primary Secondary Flow system in terms of energy efficiency. In the growing interest of energy efficiency, some engineers have now come to think that the VPF system may be employed to work better at very low load condition.
In general, this system has lower initial and operation costs compared to primary secondary flow system.
The following are the saved initial costs:
VPF system – implementation
Key to Figure 2
Liquid ΔP sensor across the variable speed pumps
This implementation is very commonly applied in most variable flow systems. Especially the hydronic configuration in the distribution circuits have manual balancing and motorised control valves. In large systems, there may be even manual balancing valves installed in the branches, risers and headers to enable proportional balancing method.
The ΔP transmitter located across the variable speed pumps has the following benefits:
Now that we know the pressure head will vary at the pumps against the system load, it is not possible for manual balancing valves to react to these variations.
For example, circuit 1 manual balancing valve is required to create a resistance of 230 kPa during full load. During part load, the available ΔP across the circuit is only 80 kPa. Hence, a manual balancing valve creates more resistance than needed when this terminal requires full flow. It is attributing under-capacity during part load.
For engineers, the biggest fear is under-capacity, which is in direct relation to their goals – comfort and efficiency.
In this scenario, the VPF system offers the most desirable implementation option.
Key to Figure 4:
Control valve authority
Most manufacturers produce typically two different valve characteristics based on Figure 6-1. The green colour character denotes the most desired character, which has no ΔP changes and, therefore, has no distortion. A stable and accurate control will require valve authority closer to 1.
If a valve authority is low, it is similar to filling a glass using a fire hose. As it opens under highly pressurised condition, water will spill over. If a valve authority is high, it is similar to filling a glass using a tap – a full range of control that precisely provides the exact flowrate that is needed.
Control valve authority in practice
The control valve authority is sized with respect to 0.5 minimum commonly as a guideline. Equation 1 has a common expression used, based on Figure 6-2:
Equation 2 is not a complete expression, because the system fittings have not been taken into account. Most of the time, chilled water systems operate two per cent full load and 98% part load.
Let us consider the worst-case scenario based on terminal unit 4 in the two diagrams: Figure 7-1 and Figure 7-2.
In essence, the denominator can be expanded, summarised and translated as in Equation 3.
PIBCV independent of pressure variations
Built-in pressure controller, DPC, takes away hydraulic influences from other parts of the installation. Regardless of different load conditions, it maintains a good valve authority.
Hence, it can be expressed, as in Equation 4.
PIBCV — a closer look
The primary task of a DP controller is to maintain constant ΔP across the control valve. When the pressure increases in P1, it inflates the bottom part (high side) of the DP controller’s chamber through capillary tubing. During inflation, the DP controller’s orifice becomes smaller to absorb pressure from P1, thus causing pressure in P2 to increase. For pressure transition chart refer to (Figure: 3-2-1).
The DP controller will shave off extra pressure applied to the control valve not only when removing hydraulic interference from other parts of the installation, but also when the control valve itself is closing. As long P1 increases, DP controller will instantly react to maintain pressure equilibrium.
We notice the DP controller’s chamber is connected to two capillary tubings that are taking both the high and low side pressures. The PIBCV is subjected to atmospheric pressure. Hence, it requires a low side capillary tubing to also achieve atmospheric pressure equilibrium.
It doesn’t matter if the DP controller is in front or behind the control valve, as long the capillary tubings are placed correctly across the control valve.
PIBCV made compact
Nothing is better than a happy union of these two components. However, an in-depth understanding will show that valve authority is not just about pressure independence. It is also subject to the actuator’s abilities to make a smarter move.
Full stroke weakness
Figure 11-1 Shows that stroke 2 was reduced from 20mm to 10mm. Stroke 1, control valve, remains 20mm as full stroke control. As shown in Figure 11-2. Stroke 1 is only effective when it is less than 50%.
If flow presetting is in a separate valve and not in the control valve itself, then the presetting will take away the control valve’s authority, reducing the control range and control authority almost to half, even though it is pressure independent.
Strokes 1 and 2 are a direct relation of (Figure 3-2-1: Pressure transition charts).
Full stroke versus stroke limitation
The diagrams shown here is to demonstrate the stroke limitation strength against full stroke. If the flow presetting is done within the control valve itself, then a good control authority can be achieved. The actuator maintains full control signal of 0-10VDC vs 0-100% flow control range after performing self-calibration
Matching the coil character
We now know that most heat exchanger’s character deviates from application to application. The next step is to determine the heat exchanger’s character and select the correct alpha value. There is a knob setting in the actuator that performs this function.
Variable primary system optimised with PIBCV
Unlike manual balancing valves (Page 8), it does not compensate pressure changes when pump speed is varying. Thus, the biggest fear of under-capacity may occur in such operations.
With PIBCV (Figure 14-2), we can rest assured that the DP controllers will perform self-balancing throughout different pump speeds. This installation will allow the system flowrate to vary in proportion to pump pressures.
ΔP sensor near to pump
ΔP sensor installed near the pumping source does not allow the pumps to run at the most optimum speed. In the diagram illustrated below, the pump pressure is constant even though system flowrate keeps varying.
ΔP sensor at critical unit
When we place the ΔP across the most critical unit, it allows the pump pressure to vary proportionally to the system curve as the flowrate reduces. Most engineers call this proportional pump control. It is illustrated in Figure 16.
PIBCV improves comfort
PIBCV eliminates low ΔT syndromes
It is evident that not only is the flowrate reduced without compromising on the cooling capacity, but there is also an improvement in the comfort level
Let’s count PIBCV’s blessings

- Elimination of secondary pumps
- No swing chiller needed
- Fewer pipe connections
- Fewer electrical connections
- Less floor space required
- Smaller bypass size
- Varying primary pump speed
- Varying compressor speed/quantity in compressors/quantity of chillers
- Efficient chiller performance even during part load

- Motorised control valves to regulate room temperature
- Motorised control valve to allow minimum flow in variable flow chillers
- Digital flowmeter
- Differential pressure sensor
- Water immersed temperature sensor
- Variable speed pumps
- Motorised isolation valves to prevent inflow from other pumps during low load
- Manual balancing valves/flow limiters or automatic balancing valves
- Modulating control valves = Regulate flow to maintain constant temperature
- Flow limiters = Regulate orifice to maintain constant flow

- Easy to troubleshoot
- Shorter cable length
- Less need for ΔP transmitter calibration
- Critical unit
- Index unit
- Reference unit

- PIBCV – Logarithmic character (water to air energy transfer)
- PIBCV – Linear character (No energy transfer)
- Digital flowmeter
- Differential pressure sensor
- Water Immersed temperature sensor
- Variable speed pumps
- Motorised isolation valves
Manual Balancing Valves / Flow limiters aka Automatic Balancing Valves




Increases comfort
- Saves energy
- Eliminates extra valves in the system
- Saves time
- Saves manpower
- Simplifies installation
- Increases the lifespan of the actuator
- Increases the lifespan of pumps, chillers, boilers and heat pumps
- No complicated conventional control valve sizing required